DROK Current Transformer, 100A 100mA AC Current Sensor, Split Core Amp Transformer Sensing Relay, Mini Clip-on Easy to Install CT Without Power Off
<p> <strong>Parameters:</strong><br /> Environment temperature: -40℃~+85℃<br /> Relative humidity: never more than 90% when the temperature is 40℃<br /> Working frequency: 50Hz~60Hz<br /> Insulation endurance grade: B grade (130℃)<br /> Insulation resistance: more than 1000MΩ normally<br /> Dielectric strength: can afford power frequency 1000V/1minute<br /> Flame resistance: Conform to UL94-Vo grade<br /> Internal resistance: 42Ω <br /> <br /> Test linear range: 0-100A<br /> 10A secondary output: 10MA<br /> 50A secondary output: 50MA<br /> 100A secondary output: 100MA<br /> Ratio is 1000: 1<br /> <br /> Range of Application:<br /> 1. The current transformer is used for energy meter in special; AC 220v, the 380v power supply can both be applied.<br /> 2. When you fix the energy meter, you don't need to cut off the power if you use this product.<br /> <br /> <strong>Precautions:</strong><br /> 1. The CT primary should be connected in series with the test current loop, the secondary should be as work in the short-circuit state<br /> 2. The secondary circuit is not allowed open circuit, so please do not install a fuse.<br /> <br /> <strong>Package Including:</strong><br /> 1x Current Transformer </p>